| Gross weight | 0.44 kg |
| Net weight | 0.37 kg |
| EAN | 5702428014571 |
| Amb. Temp. Note | 80 °C/176 °F for max 120 min |
| Ambient temperature range [°C] [Max] | 65 °C |
| Ambient temperature range [°C] [Min] | -40 °C |
| Ambient temperature range [°F] [Max] | 150 °F |
| Ambient temperature range [°F] [Min] | -40 °F |
| Approval | BV CCC CE DNV EAC GL LR LVD PZH RINA RMRS RoHS China c UL us UL873, CS C22.2 LLC CDC EURO-TYSK |
| Cap. tube length fraction [in] | 78 3/4 in |
| Capillary tube length [mm] | 2000 mm |
| Charge type | Vapour |
| Contact function | SPDT |
| Contact rating | AC15=10 A, 400 V AC1=16 A, 400 V AC3=16 A, 400 V DC13=12 W, 220 V LR=112 A, 400 V |
| Diff. @ Max. range setting [K] [Max] | 7 K |
| Diff. @ Max. range setting [K] [Min] | 1.8 K |
| Diff. @ Max. range setting[°C] [Max] | 7 °C |
| Diff. @ Max. range setting[°C] [Min] | 1.8 °C |
| Diff. @ Min. range setting [K] [Max] | 25 K |
| Diff. @ Min. range setting [K] [Min] | 4.5 K |
| Diff. @ Min. range setting[°C] [Max] | 25 °C |
| Diff. @ Min. range setting[°C] [Min] | 4.5 °C |
| Differential type | Adjustable |
| Electrical connection | Rubber cable gland |
| Electrical connection size | 6-14 mm |
| Electrical spec. standard | EN 60947-5 |
| EN 60947 electrical properties | Pollution degree: 3 Rated impulse voltage: 4 kV |