Option IO (= IO-Link Device)
Data transfer via COM3 (230,4 kBaud)
Cycle times < 3 msec
Process data IN 32 Byte (6 x process values from AX350):
• Analog value 1 (scaled / linearized) and unit
• Analog value 2 (scaled / linearized) and unit
• Analog value 1 (scaled / linearized) with totalisation and unit
• Analog value 2 (scaled / linearized) with totalisation and unit
• Shortcut analog value 1 (scaled / linearized)
with analog value 2 (scaled / linearized) and unit
• Shortcut totalisator analog value 1 (scaled / linearized)
with totalisator analog value 2 (scaled / linearized) and unit
Process data Out 8 Byte (2 x IO-Link process values to AX350):
• IOL process value Out 1 with scaling,
adjustable decimal point and programmable units
• IOL process values Out 2 with scaling,
adjustable decimal point and programmable units
Further options (can be combined):
Option AC (= Alternating Current)
Power supply:
• 115 … 230 VAC,
• 50 … 60 Hz
Option AO (= All Outputs/RS232)
4 control outputs:
• Format / level 5 … 30 VDC (external voltage COM+), PNP
• Output current max. 200 mA
• Reaction time < 1 ms
Analog output:
• Output voltage ±10 V (max. 2 mA)
or output current 0/4 … 20 mA (max. 270 Ohm)
• Resolution 16 Bit (scalable) resp. ±15 Bit
• Accuracy ±0.1 %
Serial RS232 interface:
• asynchronous data transmission
• Baudrate 9600, 19200 oder 38400 Baud
• Lecom protocol
Option AR (= All Outputs/RS485)
4 control outputs:
• Format / level 5 … 30 VDC (external voltage COM+), PNP
• Output current max. 200 mA
• Reaction time < 1 ms
Analog output:
• Output voltage ±10 V (max. 2 mA)
or output current 0/4 … 20 mA (max. 270 Ohm)
• Resolution 16 Bit (scalable) resp. ±15 Bit
• Accuracy ±0.1 %
Serial RS485 interface:
• asynchronous data transmission
• Baudrate 9600, 19200 oder 38400 Baud
• Lecom protocol
Option CO (= Control Outputs/RS232)
4 control outputs:
• Format / level 5 … 30 VDC (external voltage COM+), PNP
• Output current max. 200 mA
• Reaction time < 1 ms
Serial RS232 interface:
• asynchronous data transmission
• Baudrate 9600, 19200 oder 38400 Baud
• Lecom protocol
Option CR (= Control Outputs/RS485)
4 control outputs:
• Format / level 5 … 30 VDC (external voltage COM+), PNP
• Output current max. 200 mA
• Reaction time < 1 ms
Serial RS485 interface:
• asynchronous data transmission
• Baudrate 9600, 19200 oder 38400 Baud
• Lecom protocol
Option RL (= Relais)
2 output relays with potential-free change over:
• Switching capacity (AC) max. 250 VAC / 3 A / 750 VA
• Switching capacity (DC) max. 150 VDC / 2 A / 50 W
• Reaction time < 20 ms